10 CHANNEL ANALOGUE AUDIO WITH PRIORITY LINE

The CX10 is an audio control unit that allows a single channel priority signal to be routed into all channels of a audio system, simultaneously attenuating existing audio. The priority input gain is adjustable, also the amount of fade down of the main channels can be set. These settings are on the rear panel via recessed potentiometers. The CX1 0 also has a test facility and connections for remote monitoring. A push switch allows a quick and easy test of operation to be made.

Triggered by shorting a pair of pins on the rear panel, the CX1 0 can be linked to a fire alarm for evacuation announcements or any other requirement where 1 signal is required to take priority over all others.

Each channel level can be adjusted via recessed potentiometers behind the front panel.

Balanced inputs and outputs (that can be strapped for unbalanced operation) on all 10 channels and the priority input.

An LED on the front panel indicates when priority is triggered.

The remote monitoring facility can be used to indicate the test status and that the equipment is powered/functional.

The CX1 0 has been designed to be connected between the mixer (or pre-amp) of an audio system and the power amplifiers.

The unit may be connected to 10 channels of audio.

The priority signal (eg. emergency microphone) is connected to the priority input socket. This is a line level input. The control input is connected to the triggering device (a fire alarm or an isolated switch etc). When the unit is triggered the programme llevel in all ten channels is attenuted and the priority input automatically mixed into all ten outputs.

When the trigger is switched off or removed the programme will fade back to its original level. The amount of programme attenution is adjustable between 0 - 90 dB All controls are operated through holes in the front and rear panels for security and to avoid accidental changes to settings.

The priority signal (eg emergency microphone etc) is connected to the priority input socket. This is a line level input.

The control input is connected to the triggering device (a fire alarm or and isolated switch etc). When the unit is triggered the programme level in all ten channels is attenuted and the priority input automatically mixed into all ten outputs.

When the trigger is switched off or removed the programme will fade back to its original level.

The amount of programme attenution is adjustable between 0 - 90 dB

All controls are operated through holes in the front and rear panels for security and to avoid accidental changes to settings.

CX 10 Technical Specification

Frequency Response: 20Hz - 20Khz +/- 0.5 dB
Distortion THD+Noise: @ 1Khz Noise: O/P Level +20dBu <0.015%
Noise 20Hz - 20Khz: EIN < -90dBu

Inputs:
Electronically balanced, connect negative to screen for unbalanced use.
Input impedance: Balanced 20K Ohms
Unbalanced 10K Ohms
Maximum input level: Clip indicator: +22dBu Indicates @ +20dBu

Outputs:
Minimum load impedance: 600 Ohms
Electronically balanced, connect negative to screen for unbalanced use.
Source impedance: 100 Ohms

Controls:
Level - priority input level into all channels - rear panel
Atten - Attenuation of channels in priority mode - rear panel
1 -10 - Channel level - front panel

Attenution:
Main channels attenuate by 0 to 90dB (adjustable) on prioity

Priority input:
Input impedance> 20K Ohms, Unbalanced < 10K Ohms. Mximum input +22dBu

Control input monitoring:
Switch contacts. Close to operate. Must be isolated. Power supply monitoring via opening/closing contacts.

Visual indicators :
Power - 2 Green LED's, Priority 1 - Red LED, all on front panel

Power:
220V - 240V (110V to order).
IEC Mains connector; mains fuse 250mA slow blow.

Finish:
Front and Rear panels - Black anodised aluminium with silver legend. Case - Black plastic coated steel.

Dimensions:
19" Rack mounting, 1RU

Width 482mm (19") Depth 200mm (7.9") Height 44mm (1.75")

Download CX10 Users Instruction Manual

Rating: 4 4/5 based on 2 customer ratings
Reviews

Formula Sound CX10 Priority / Evacuation System - formulasounddirect.com



Formula Sound News Headlines

Verstappen summoned over Russell incident in Qatar qualifying 2024-11-30
formula 1 world champion Max Verstappen has been summoned to the Qatar Grand Prix stewards for driving unnecessarily slowly during qualifying, in which he appeared to block George Russell.The Red Bull driver, who clinched his first grand prix pole since June'…
F1 will be a 'battle of giants' with GM - RB boss 2024-11-30
formula 1 will become even more a "battle of giants" with the arrival of General Motors' Cadillac brand as an 11th team in 2026, according to RB boss Laurent Mekies.
Exclusive: F1 racing guidelines set to change no earlier than 2025 2024-11-30
formula 1’s controversial racing guidelines will now not change until the 2025 season, Autosport can reveal.The topic has been a huge discussion point as the current campaign has played out – with the FIA committing to reassessing the ‘Driving Standards Guide…

See the FF6000 in action


Tuesday 03 December 2024